loading

Richtek Load Transient Tool

RD0004

Share

The Richtek Load Transient Tool can generate very fast load steps (~500nsec rise/fall times), and can be used to quickly verify pulse load behaviour of voltage regulators. It can be used to check DC/DC converter stability, layout resonance, input supply ringing, etc. 7 different pulse load resistors can be selected via jumpers, and an adjustable power resistor is used for setting the static load level. Pulse load frequency and duty-cycle can be adjusted via push-buttons. The tool is battery powered which makes it easy to apply at any point in your application.

Load Transient Tool features:

  • 7 selectable 1W pulse load resistors 0.5Ω ~ 22Ω
  • Adjustable 10Ω/10W resistor for static load
  • Adjustable duty-cycle from 0.1% ~ 50%
  • Adjustable frequency from 15Hz to 976Hz in 4 steps.
  • 500nsec pulse load rise/fall times
  • Highly suitable for testing DC/DC buck converters with 1~5V output and 1~5A load
  • Can also be used for testing LDO, boost, buck-boost converters.

For more information on the Richtek Load Transient Tool,
please contact your local Richtek sales office.

Adobe Systems

Figure 1: Richtek Load Transient Tool connections and functions

The Richtek Load Transient Tool contains a micro controller that switches a MOSFET on and off with a certain duty-cycle. When connected to a voltage regulator output, the MOSFET switches a load resistor on and off, thereby creating a fast changing pulse load. The tool can generate very fast load steps (~500nsec rise/fall times), and can be applied to any voltage regulator output in your system. My measuring the regulator output voltage during the fast load step, the regulator control loop behaviour can be observed.

Technical Document Image Preview

Figure 2: Basic Load Transient measurement method


Adobe Systems

Figure 3: Practical Load Transient Tool measurement setup

A fast load step will excite the system control loop over a wide frequency range. Control loop instability or under damped response can be seen as output voltage ringing. This is only valid for CCM (continuous current mode) operation, so PSM-CCM transitions should be avoided. Always adjust the static load for CCM operation range during the load step.

Figure 4 shows an example of a poor and a good load step response of a 3.3V / 3A converter. The example on the left side shows that the regulator output voltage has severe ringing after a load transient, indicating that the control loop has marginal stability. In most cases this is related to the converter feedback loop compensation in combination with the output capacitor value.

Technical Document Image Preview

Figure 4: example of poor and good load step response

Besides control loop stability issues, other resonance effects due to layout parasitic trace inductance, input supply ringing etc. can also be quickly identified with the fast load transient tool.

Technical Document Image Preview

Figure 5: Load Transient Tool schematic

The schematic in figure 5 shows the the micro controller which drives the MOSFET switch. The MOSFET gate drive is designed to generate equal switching speeds with ~500nsec rise/fall times. Reducing or removing C2 can increase the switching speed, but the actual load current transient speed will be mostly determined by the wiring inductance between the tool and the application. Especially when testing low voltage supplies (< 2V), it may be necessary to use short, thick wires between the tool and the application to minimize inductance, see figure 6.

Technical Document Image Preview

Figure 6: Reducing wire inductance between transient tool and application for faster load step speed.

The tool consists of a load transient board, an adjustable power resistor for setting static load and battery pack, see figure 7.

Technical Document Image Preview

Figure 7: Richtek Fast Load Transient Tool kit.

Guidelines for use:

  1. Insert 3x1.5V AAA batteries in the battery holder. Please note the correct polarity.
  2. Connect the power jumper: Power LED lights for 1 second, and then flashes once per second. (Default start-up frequency is 244Hz with 5% pulse load duty-cycle).
  3. Connect the Load_2 & GND connection to regulator output.
  4. Connect the adjustable 10Ω power resistor to the static load pins. Adjust the slider for low level load current to be in CCM mode (or ~30% of regulator max load).
  5. Insert the jumper to JP1~JP7 for desired pulse load resistor (suggestion for stability check: VOUT/RLOAD ≈ 30% of maximum converter load)
  6. Measure the pulse load current in the load wire and observe voltage regulator output during load transient. Ringing in the voltage waveform can point to insufficient stability.
  7. The PULSE output can be connected to scope ext sync. Note that doing this can create ground loops and the regulator output voltage reading may be affected.
  8. The pulse load duty-cycle can be adjusted by pressing UP and DOWN buttons. The adjustment range is 0.1% ~ 50%. The power LED will flash quickly when end of adjustment range is reached. Note that the power dissipation in the pulse load resistors increases when duty-cycle is increased. Do not exceed 1W average power!
  9. The pulse load frequency can be changed by pressing FREQ + UP or DOWN buttons together. The frequency adjustment range has 4 steps: 15Hz, 61Hz, 244Hz (default) and 976Hz. The power LED will flash quickly when end of adjustment range is reached. Duty-cycle is maintained when changing frequency.
  10. Remove the power jumper to stop the pulse load generator. Static load will remain.
  11. Re-insert power jumper will reset pulse load duty-cycle to 5% and frequency to 244Hz.

For more information on converter loop stability and load transient testing, please read the application note AN038
DC/DC converter testing with Fast Load Transient

Title Last Update Share Download
Load Transient Tool User Manual 2020/12/02
Application Note: DC/DC converter testing with Fast Load Transient 2017/11/15
Design Tip: How to use Richtek Fast Load Transient Tool to check Buck Converter Stability 2017/04/06
Design Tip: A simple way to test buck converter stability 2017/04/06
[Video] How to estimate control loop bandwidth from the transient response time? 2017/04/19
Part NumberDistributorStockBuy From Authorized Distributor
RD0004 Digikey 12 Buy
Mouser 0 Lead-Time: 14 weeks
TOP